GH1
Checking verified climate feed
Maintenance readout for greenhouse temperature, heat demand, circulation, and boiler response across GH1–GH3. Missing or delayed measurements are explicitly shown as unavailable.
Crop-facing measurements · Fahrenheit
Checking verified climate feed
Awaiting mapped temperature feed
Awaiting mapped temperature feed
Priva Zone 3 working assignment · requires live output mapping
Checking 15-minute trend
Waiting for trend observations.
On-page review only · not phone notifications
Proposed starting criteria · not armed
| Event | Signals required | Proposed first-pass criterion | Recommended response |
|---|---|---|---|
| Crop temperature deficit | Fresh air temp + effective heating setpoint | Below effective target by 4°F for 20 minutes while heat is requested | Check heat supply and crop temperature; escalate if persistent |
| Rapid temperature decline | At least 30–60 minutes of fresh temperature history | Decline of 4°F/hour or faster, with outdoor cold exposure | Verify vents, curtains, boiler and circulation |
| Supply failing under demand | Desired + measured supply temperatures; demand | Supply more than 30°F below requested for 15 minutes while heat demand remains high | Check boiler enable, fault, flame, fuel and pump feedback |
| Distribution problem | Supply temp, valve command, measured pipe temp, zone response | Hot supply available but cold pipe/crop persists during demand | Investigate valve, pump, air lock or distribution issue |
| Critical crop / freeze exposure | Fresh, independently verified greenhouse temperatures | Crop-specific critical temperatures and duration, confirmed by grower | Immediate operator escalation; check local Priva alarms |
| Telemetry unavailable | Per-sensor timestamps and pipeline heartbeat | New readings not received within 15 minutes; escalation if prolonged | Check data pipeline; never display stale data as healthy |